Location
United States
Application
NH₃ plant + BOG handling
Capacity
40 t/h
Cooling
−37 / −5 / +5 °C
Project overview
Turnkey delivery for a major North American ammonia producer.
Technofrigo by Clauger delivered a complete process refrigeration system for a major North American petrochemical client producing ammonia. This turnkey installation provides multi-level cooling for process applications while safely handling boil-off gas from ammonia storage tanks — a critical requirement for continuous plant operations in high-ambient-temperature conditions.
The client
We worked directly with a major engineering and petrochemical group delivering technology, engineering, procurement and construction for synthesis gas, air separation, petrochemical plants, and fluid processing for refineries.
Why BOG management matters
Industrial ammonia storage requires large, low-pressure tanks maintained at low temperatures. In high-temperature seasons, heat transfer to storage tanks creates vapour or boil-off gas. Without proper management, this results in product loss, safety concerns and operational inefficiencies. Active refrigeration — not tank insulation alone — is essential for reliable operations.
The challenge
Three precise cooling levels plus BOG handling.
The client required a full-scale refrigeration system supplying cooling at three precise temperature levels to support ammonia production and storage operations, plus safe handling of vapour from storage tanks.
Process refrigeration requirements
- Three-level cooling: −37 °C, −5 °C and +5 °C
- Processing capacity of 40 t/h for the ammonia plant
- Integration with existing ammonia production operations
- Turnkey delivery with complete engineering and execution
Boil-off gas management
- Safe handling of vapour formation (BOG) from ammonia storage tanks during high-ambient periods
- Condensing boil-off flow during plant shut-down
- Managing flash gases generated when re-liquefied ammonia returns to storage
- Maintaining storage integrity while minimising ammonia losses


Our solution
Integrated refrigeration & BOG architecture.
We engineered a complete ammonia-based refrigeration system integrating process cooling with boil-off-gas handling — delivering reliable performance across all operating conditions including extreme temperatures.
Multi-level refrigeration system
The process refrigeration system features three oil-flooded screw compressors operating at three different pressure levels.
- Processing of various process vapour streams at different temperatures
- Heat exchangers and drum separators completing the refrigeration cycle
- Efficient heat transfer across the required temperature range (−37 °C to +5 °C)
- Reliable operation for continuous ammonia production
Boil-off gas (BOG) package
The dedicated BOG system safely handles vapour streams from ammonia storage.
- Ammonia screw compressor — compresses ammonia gas from storage-tank boil-off
- Condensation system — returns compressed gas to liquid state for tank return
- Flash-gas handling — manages vapour generated during re-liquefaction and tank return
- Shut-down cooling — condenses boil-off flow during plant shut-down periods
- Heat-load management — transfers heat from low to high temperatures as required
Technical specifications
The numbers at a glance.
Performance and architecture in summary — full design dossiers available on request under NDA.
| Refrigeration capacity | 40 t/h processing capacity |
| Cooling levels | Three: −37 °C, −5 °C, +5 °C |
| Process compressors | Three oil-flooded screw compressors (multi-pressure) |
| BOG compressor | One ammonia screw compressor |
| Refrigerant | Ammonia (NH₃) — natural, efficient refrigerant |
| Application | NH₃ production plant + storage-tank BOG management |
| Delivery scope | Complete turnkey system — design, engineering, supply, installation |
| Site condition | High-ambient temperature operating envelope |
Project impact
What this installation actually delivers.
Impact 01
Process reliability
Three-level cooling ensures continuous ammonia production operations through the year.
Impact 02
Product conservation
BOG condensation eliminates ammonia losses from storage tanks during high-ambient periods.
Impact 03
Safe storage
Proper vapour management reduces pressure risks in ammonia storage operations.
Impact 04
Operational flexibility
System handles normal operations and plant shut-down scenarios reliably.
Impact 05
Extreme-temp performance
Proven effective in demanding ambient conditions where other systems struggle.
Impact 06
Natural refrigerant
Ammonia-based system provides efficient, cost-effective cooling — ideal for plants already handling NH₃.
Working on a similar project?
Send us the broad strokes of your application — we’ll route your enquiry to the engineers who delivered installations like this one.